1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
141
Pa
ra
m
et
er D
et
ai
ls
1
Figure 1.45
Figure 1.45 3-Wire Sequence
Note:
1.
The Run and Stop command must be open/closed for a short moment only to start and stop the drive.
2.
If the Run command is active at power up and b1-17 = 0 (Run command at power up not accepted), the
Run LED will flash to indicate that protective functions are operating. If required by the application, set
b1-17 to 1 to have the Run command issued automatically as soon as the drive is powered up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly in reverse direction after power
up if it is wired for 3-wire sequence but set up for 2-wire sequence (default). When using 3-wire sequence
first set the drive properly (H1-
= 0) and then connect the control wires. Make sure b1-17 is set to “0”
(drive does not accept Run command active at power up). When initializing the drive use 3-wire initialization.
Failure to comply could result in death or serious injury from moving equipment.
Setting 1: LOCAL/REMOTE Selection
This setting allows the input terminal to determine if the drive will run in LOCAL mode or
REMOTE mode.
Note:
1.
If one of the multi-function input terminals is set to for LOCAL/REMOTE, then the LO/RE key on the
operator will be disabled.
2.
When the drive is set to LOCAL, the LO/RE LED will light.
3.
The default setting of the drive is not to allow switching between LOCAL and REMOTE during run.
Refer to
b1-07: LOCAL/REMOTE Run Selection on page 45
if this feature is required by the
application.
Status
Description
Open
LOCAL: Frequency reference and Run command are input from the digital operator.
Closed
REMOTE: Frequency reference and Run command are input from the selected external
reference. If no input is set to H1-
= 2 the settings in parameters b1-01/02 are valid. If
a digital input set to H1-
= 2, the source selected by this input will be valid.
Run command
OFF (stopped)
ON (reverse)
Stop
Reverse
Stop
Foward
TIME
Can be either ON or OFF
OFF (forward)
Forward
Motor speed
Forward/reverse
command
Stop command