A.2 Parameter Table
370
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
U4-02
Number of Run
Commands
Displays the number of times the run
command is entered. Reset the number of run
commands using parameter o4-13. This value
will reset to 0 and start counting again after
reaching 65535.
No signal
output avail.
A A A
75
U4-03
Cooling Fan Operation
Time
Displays the cumulative operation time of the
cooling fan. The default value for the fan
operation time is reset in parameter o4-03.
This value will reset to 0 and start counting
again after reaching 99999.
No signal
output avail.
1 h A A A
67
U4-04
Cooling Fan
Maintenance
Displays main cooling fan usage time in as a
percentage of their expected performance life.
Parameter o4-03 can be used to reset this
monitor.
No signal
output avail.
1% A A A
7E
U4-05
Capacitor
Maintenance
Displays main circuit capacitor usage time in
as a percentage of their expected performance
life. Parameter o4-06 can be used to reset this
monitor.
No signal
output avail.
1% A A A
7C
U4-06
Soft Charge Bypass
Relay Maintenance
Displays the soft charge bypass relay
maintenance time as a percentage of the
estimated product life. Parameter o4-07 can
be used to reset this monitor.
No signal
output avail.
1% A A A
7D6
U4-07 IGBT Maintenance
Displays IGBT usage time as a percent of
expected performance life. Parameter o4-09
can be used to reset this monitor.
No signal
output avail.
1% A A A
7D7
U4-08
Heatsink Temperature
Displays the heatsink temperature.
No signal
output avail.
1
°
C A A A
68
U4-09 LED Check
Lights all segments of the LED to verify that
the display is working properly.
No signal
output avail.
–
A A A
3C
U4-10 kWH, Lower 4 Digits Monitors the drive output power. The value is
shown as a 9 digit number displayed across
two monitor parameters, U4-10 and U4-11.
Example:
12345678.9 kWh is displayed as:
U4-10: 678.9 kWh
U4-11: 12345 MWh
No signal
output avail.
kWh A A A
5C
U4-11 kWH, Upper 5 Digits
MW
h
A A A
5D
U4-13 Peak Hold Current
Displays the peak hold current during run.
10 V: Motor
rated current
0.01
A
A A A
7CF
U4-14
Peak Hold Output
Frequency
Displays the output frequency when operating
at the peak hold current.
10 V: Max
frequency
0.01
Hz
A A A
7D0
No.
Name
Description
Analog
Output Level
Unit
Control
Mode Addr.
Hex
V/f
O
LV
P