2.9 MEMOBUS/Modbus Data Table
276
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
◆
Monitor Data
Monitor data can be read only.
0009H
Settings for Multi-Function Digital Outputs
bit 0
Contact Output (terminal MA/MB-MC)
bit 1
Photocoupler Output 1 (terminal P1-PC)
bit 2
Photocoupler Output 2 (terminal P2-PC)
bit 3 to bit 5
Reserved
bit 6
Enable Fault Contact Output (1 = enable bit 7)
bit 7
Fault Contact (terminal MA/MB-MC)
bit 8 to bit F
Reserved
000AH
Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000
000BH-000EH
Reserved
000FH
Control Selection Setting
bit 0
Reserved
bit 1
PID Target Input
bit 2 to bit B
Reserved
bit C
Enable Terminal S5 Input for Broadcast Data
bit D
Enable Terminal S6 Input for Broadcast Data
bit E
Reserved
bit F
Reserved
Register No.
Contents
0020H
Drive Status 1
bit 0
During Run
bit 1
During Reverse
bit 2
Drive Ready
bit 3
Fault
bit 4
Data Setting Error
bit 5
Multi-Function Contact Output (terminal MA/MB-MC)
bit 6
Multi-Function Photocoupler Output 1 (terminal P1 - PC)
bit 7
Multi-Function Photocoupler Output 2 (terminal P2 - PC)
bit 8 to bit D
Reserved
bit E
ComRef status
bit F
ComCtrl status
Register No.
Contents