A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
327
Para
me
te
r Lis
t
A
◆
H Parameters: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
F7-09
Gateway Address 1
Combining these parameters like F7-09.F7-
10.F7-11.F7-12 sets the Ethernet Gateway
Address.Example: (192.168.1.1).
0 to 255
192
A A A
3ED
F7-10
Gateway Address 2
0 to 255
168
A A A
3EE
F7-11
Gateway Address 3
0 to 255
1
A A A
3EF
F7-12
Gateway Address 4
0 to 255
1
A A A
3F0
F7-13
Address Mode at
Startup
Selects how the Ethernet IP address is set.
0:User defined
1:BOOTP
2:DHCP
0
A A A
3F1
F7-14
Duplex Mode
Selection
0:Auto Negotiate
1:Half Duplex forced
2:Full Duplex forced
0
A A A
3F2
Communication Speed
Selection
0:Auto Negotiate
10:10 Mbps speed setting
100:100Mbps Speed Setting
100
0
A A A
3F3
Communication Loss
Timeout
Sets the timeout value for communication loss
detection.
0 to 300
0
A A A
3F4
F7-17
Ethernet Speed
Scaling Factor
Sets the scaling factor for the speed monitor in
Ethernet Class ID 2AH Object.
-15 to
15
0
A A A
3F5
Ethernet Current
Scaling Factor
Sets the scaling factor for the output current
monitor in Ethernet Class ID 2AH Object.
-15 to
15
0
A A A
3F6
F7-19
Ethernet Torque
Scaling Factor
Sets the scaling factor for the torque monitor in
Ethernet Class ID 2AH Object.
-15 to
15
0
A A A
3F7
F7-20
Ethernet Power
Scaling Factor
Sets the scaling factor for the power monitor in
Ethernet Class ID 2AH Object.
-15 to
15
0
A A A
3F8
F7-21
Ethernet Voltage
Scaling Factor
Sets the scaling factor for the voltage monitor in
Ethernet Class ID 2AH Object.
-15 to
15
0
A A A
3F9
F7-22
Ethernet Time Scaling
Sets the scaling factor for the time monitor in
Ethernet Class ID 2AH Object.
-15 to
15
0
A A A
3FA
<58> Valid from drive software 1011 and later. Parameters F6-50 to F6-54 had parameter numbers F6-20 to F6-24 in
older software.
<59> Available in drive software 1011 and later.
<60> Default Setting valid for drive software 1011 and later.
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M