1.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
131
Pa
ra
m
et
er D
et
ai
ls
1
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast Stop Using C1-09
Setting 3: Alarm only, Continue Operation
■
F6-04: Bus Error Detection Time
Sets the delay time for a “bUS” error detection.
■
F6-10: CC-Link Node Address
Sets the node address of a CC-Link option board if installed.
■
F6-11: CC-Link Communication Speed
Sets the communication speed for a CC-Link option card if installed.
Settings:
■
F6-14: BUS Error Auto Reset
Selects if a BUS error can be automatically reset if automatic fault retry is enabled.
No.
Parameter Name
Setting Range
Default
F6-04
Bus Error Detection Time
0.0 to 5.0 s
2.0 s
No.
Parameter Name
Setting Range
Default
F6-10
CC-Link Node Address
0 to 63
0
No.
Parameter Name
Setting Range
Default
F6-11
CC-Link Communication Speed
0 to 4
0
F6-11
Communication Speed
F6-11
Communication Speed
0
156 kbps
3
5 Mbps
1
625 kbps
4
10 Mbps
2
2.5 Mbps
No.
Parameter Name
Setting Range
Default
F6-14
BUS Error Auto Reset
0 or 1
0