1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
155
Pa
ra
m
et
er D
et
ai
ls
1
4
Multi-Step
Speed
Reference
> 0
--
0
• When the Up 2 is enabled, drive
accelerates up to the frequency
reference plus d4-03 (bias is
increased for d4-03).
• When Down 2 is enabled, drive
decelerates down to the frequency
reference minus d4-03 (bias is
decreased for d4-03).
• Holds output frequency (holds the
bias) when no Up 2 or Down 2 input
or both active.
• Resets the bias when the reference
changes
• Operates with the frequency
reference in all other situations.
Not saved
5
1
If the bias and frequency
reference are constant for 5 s,
the bias is added to the active
frequency reference and reset
afterwards.
6
Other
(analog
communic
ations, etc.)
0
0
0
• Accelerates (increases the bias) while
the Up 2 function is closed
• Decelerates (decreases the bias)
while Down 2 is closed
• Holds output frequency (holds the
bias) when no Up 2 or Down 2 input
or both active.
• When during accel/decel. the
frequency reference changes for
more then d4-07, bias value is held
until the output frequency meets the
reference (speed agree).
Not saved
7
1
If the bias is constant for 5 s, is
is saved to parameter d4-06.
The frequency reference cannot
be overwritten, so only the bias
is saved.
8
Other:
Analog,
Comm.,
etc.)
0
1
--
• Accelerates (increases the bias) while
the Up 2 function is closed,
• Decelerates (decreases the bias)
while Down 2 is closed.
• Otherwise operates at the frequency
reference
Not saved
9
>0
--
0
• When the Up 2 is enabled, drive
accelerates up to the frequency
reference plus d4-03 (increases the
bias for d4-03).
• When Down 2 is enabled, drive
decelerates down to the frequency
reference minus d4-03 (decreases the
bias for d4-03).
• When during accel/decel the
frequency reference changes for
more then d4-07, bias value is held
until the output frequency meets the
reference (speed agree).
Not saved
10
1
If the bias is constant for 5 s, is
is saved to parameter d4-06.
The frequency reference cannot
be overwritten, so only the bias
is saved.
Con-
dition
Freq. Ref.
Source
d4-03 d4-05 d4-01
Operation
Frequency Saved