1.6 F: Option Settings
138
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
■
F7-17 to F7-22: EtherNet Scaling Factors
These parameters define scaling factors for drive monitors in the EtherNet Class ID 2AH -
AC Drive Object.
Setting
The monitor value in the Class 2AH - AC Drive Object is calculated by:
Class 2AH Object Monitor = Drive Value x 2
Scaling
Example:
If the drive output frequency monitor (U1-02) is 50.0 and the scaling is set to F7-17 = 3, then
the value in the Class 2AH - AC Drive Object, Instance 1, Attribute 7 would be 500 x 2
3
=
4000.
<1> Valid from drive firmware version 1011 and later. Parameter number was F7-21 in older software.
No.
Parameter Name
Setting Range
Default
F7-17
<1> Valid from drive firmware version 1011 and later.
EtherNet Speed Scaling
-15 to 15
0
F7-18
EtherNet Current Scaling
-15 to 15
0
F7-19
EtherNet Torque Scaling
-15 to 15
0
F7-20
EtherNet Power Scaling
-15 to 15
0
F7-21
EtherNet Voltage Scaling
-15 to 15
0
F6-22
EtherNet Time Scaling
-15 to 15
0