When set to “F”, the output is not set by any drive function but it can be switched by a PLC
via a communication option or MEMOBUS/Modbus communications (through mode).
Setting 10: Minor Fault
Output closes when a minor fault condition is present.
Setting 11: Reset Command Active
Output closes whenever there is an attempt to reset a fault situation from the control circuit
terminals, via serial communications, or using a communications option card.
Setting 12: Timer Output
This setting configures a digital output terminal as output for the timer function. Refer to
for details.
Setting 13: Speed Agree 2 (fref / fout Agree 2)
Closes whenever the actual output frequency is within the Speed Agree Width (L4-04) of the
current frequency reference regardless of the direction.
Note:
The detection works in both forward and reverse.
Figure 1.59
Figure 1.59 Speed Agree 2 Timechart
Status
Description
Open
Output frequency does not match the frequency reference while the drive is running
Closed
Output frequency is within the range of frequency reference ± L4-04
Frequency
reference
Output
frequency
L4-04
L4-04
Speed Agree 2
ON
OFF