8. COMMUNICATION DATA LIST
IMS01T28-E4
8-11
Continued from the previous page.
No. Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
18
Force ON of Event 1
action
OA CH1
CH2
01BA
01BB
442
443
7 R/W
1
C
RKC communication
Least significant digit:
Event output turned on at
input error occurrence
2nd digit: Event output turned on in
Manual mode
3rd digit: Event output turned on
during the Autotuning
(AT) function is being
executed
4th digit: Event output turned on
during the Setting change
rate limiter is being
operated
5th digit to Most significant digit:
Unused
Data
0: Invalid
1: Valid
Modbus
Bit data
Bit 0: Event output turned on at
input error occurrence
Bit 1: Event output turned on in
Manual
mode
Bit 2: Event output turned on during
the Autotuning (AT) function
is being executed
Bit 3: Event output turned on during
the Setting change rate limiter
is being operated
Bit 4 to Bit b15: Unused
Data 0: Invalid
1: Valid
[Decimal number: 0 to 15]
0
19
Event 2 type
XB
CH1
CH2
01BE
01BF
446
447
7 R/W
1
C 0: None
1: Deviation high
(Using SV monitor value) *
2: Deviation low
(Using SV monitor value) *
3: Deviation high/low
(Using SV monitor value) *
4: Band (Using SV monitor value) *
5: Process high *
6: Process low *
7: SV high
8: SV low
9: Unused
10: MV high *
11: MV low *
12: Unused
13: Unused
14: Deviation high (Using local SV) *
15: Deviation low (Using local SV) *
16: Deviation high/low
(Using local SV) *
17: Band (Using local SV) *
18: Deviation between channels high
*
19: Deviation between channels low *
20: Deviation between channels
high/low
*
21: Deviation between channels
band
*
* Event hold action is available.
Based on
model code
When not
specifying: 0
1
During RUN (control), the attribute of Engineering setting data is RO. To configure Engineering setting data, the RUN/STOP switch must
be set to STOP (control stopped).
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...