9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-62
Continued from the previous page.
Example: When “0: Event output turned on at input error occurrence” is selected
Input range:
50.000 to +150.000
C
Input error determination point (high): 100.000
C
Input error determination point (low): 0.000
C
Action area at input error
Action area at input error
Differential gap
(0.1 % of input span)
Input error determination point
(high)
50.000
C
0.000
C
100.000
C 150.000
C
Input scale range
Forcibly turned on
(1: Valid)
Normal processing
(0: Invalid)
Forcibly turned on
(1: Valid)
Normal processing
(0: Invalid)
Select one of these
Input error determination point
(low)
Select one of these
“
0: Invalid”: The event output is produced depending on the selected event action status.
“
1: Valid”: The event output is forcibly turned on regardless of the event action status.