8.4 Memory Area Data Address
For data operation, refer to
7.4 How to Use Memory Area Data (P.7-13)
.
No. Name
Chan-
nel
Register address Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
1
Setting memory area
number
CH1
CH2
0500
0501
1280
1281
R/W C 1 to 8
1
2
Event 1 set value (EV1)
CH1
CH2
0504
0505
1284
1285
R/W C Deviation action, Deviation action between
channels:
Input span to +Input span *
Process action, SV action:
Input scale low to Input scale high *
MV action:
5.0 to +105.0 %
If the Event type corresponds to “0: None,” set to RO
(Only reading data is possible).
If Event 4 corresponds to “9: Control loop break
alarm (LBA),” the Event 4 set value becomes RO
(Only reading data is possible).
*
Varies with the setting of the decimal point
position. However, even if "3: Three decimal
places" is set, the maximum settable decimal places
are 2.
50.00
3
Event 2 set value (EV2)
CH1
CH2
0508
0509
1288
1289
R/W C
50.00
4
Event 3 set value (EV3)
CH1
CH2
050C
050D
1292
1293
R/W C
50.00
5
Event 4 set value (EV4)
CH1
CH2
0510
0511
1296
1297
R/W C
50.00
6
Control loop break alarm
(LBA) time
CH1
CH2
0514
0515
1300
1301
R/W C 0 to 7200 seconds
(0: Unused)
480
7 LBA
deadband
CH1
CH2
0518
0519
1304
1305
R/W C 0 (0.0, 0.00) to Input span
Varies with the setting of the decimal point position.
However, even if "3: Three decimal places" is set, the
maximum settable decimal places are 2.
0.00
8
Set value (SV)
CH1
CH2
051C
051D
1308
1309
R/W C Setting limiter low to
Setting limiter high
Varies with the setting of the decimal point position.
RTD input:
0.00 (0.000)
V input:
0.000
9
Proportional band
[heat-side]
CH1
CH2
0520
0521
1312
1313
R/W C RTD input:
0 (0.0, 0.00) to Input span
(Unit:
C)
Varies with the setting of the decimal point
position. However, even if "3: Three decimal
places" is set, the maximum settable decimal places
are 2.
Voltage (V) input:
0.00 to 300.00 % of input span
0 (0.0, 0.00): ON/OFF action
30.00
10
Integral time [heat-side]
CH1
CH2
0524
0525
1316
1317
R/W C 0.0 to 3000.0 seconds
(0.0: PD action)
240.0
11
Derivative time
[heat-side]
CH1
CH2
0528
0529
1320
1321
R/W C 0.0 to 3000.0 seconds
(0.0: PI action)
60.0
12
Control response
parameter
CH1
CH2
052C
052D
1324
1325
R/W C 0: Slow
1: Medium
2: Fast
[Internally fixed to Fast in case of P and PD actions.]
0
13 Manual
reset
CH1
CH2
0540
0541
1344
1345
R/W C
100.0 to +100.0 %
If the Integral function is valid, set to RO (Only
reading data is possible).
When Integral time is zero, manual reset value is
added to the control output.
0.0
14
Setting change rate limiter
(up)
CH1
CH2
0544
0545
1348
1349
R/W C 0 (0.0, 0.00) to
Input span/unit time *
0 (0.0, 0.00): Unused
Varies with the setting of the decimal point position.
However, even if "3: Three decimal places" is set, the
maximum settable decimal places are 2.
* Unit time: 60 seconds (factory set value)
0.00
15
Setting change rate limiter
(down)
CH1
CH2
0548
0549
1352
1353
R/W C
0.00
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...