9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-4
Comprehensive event state
RKC communication
identifier
AJ
Modbus
register address
ch1: 0004H (4)
ch2: 0005H (5)
Each event state such as Event 1 to Event 4 or Burnout is expressed in bit data items.
Attribute:
RO
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
RKC communication:
ASCII code data
The event state is assigned as a digit image in ASCII code data of 7 digits.
ASCII code data of 7 digits:
Most significant digit ············ Least significant digit
Data:
0: OFF 1: ON
Modbus:
0 to 79 (bit data)
The event state is assigned as a bit image in binary numbers.
Bit image: 0000000000000000
Bit 15 ······················ Bit 0
Bit data: 0: OFF
1: ON
Factory set value:
Related parameters:
Event set value (EV) (P. 9-19), Burnout direction (P. 9-49),
Event type (P. 9-52), Event hold action (P. 9-55),
Event interlock (P. 9-57), Event differential gap (P. 9-58),
Event delay timer (P. 9-59)
Bit 0:
Event 1
Bit 1:
Event 2
Bit 2:
Event 3
Bit 3:
Event 4
Bit 4:
Unused
Bit 5:
Unused
Bit 6:
Burnout
Bit 7 to Bit 15: Unused
Least significant digit: Event 1
2nd digit:
Event 2
3rd digit:
Event 3
4th digit:
Event 4
5th digit:
Unused
6th digit:
Unused
Most significant digit: Burnout
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...