11. SPECIFICATIONS
IMS01T28-E4
11-6
Indication lamp
Number of indicates:
2 points
Indication contents:
Operation state indication (1 point)
When normal (RUN):
A green lamp is on
Control is stopped due to the self-diagnosis (FAIL):
A green lamp flashes
Action is stopped due to the self-diagnosis (FAIL):
A red lamp is on
Communication state indication (1 point)
During data send and receive (RX/TX):
A green lamp turns on
Control
Control method:
Brilliant II PID control (Direct action/Reverse action is selectable)
Autotuning (AT):
Enhanced AT (Brilliant II PID control)
Brilliant II PID control
Overshoot suppression function:
Reset feedback (RFB)
Setting range:
a)
Proportional
band
(P)
*
RTD input:
0 (0.0, 0.00) to Input span (unit:
C)
Varies with the setting of the decimal point position.
However, even if "3: Three decimal places" is set, the
maximum settable decimal places are 2.
Voltage input:
0.00 to 300.00
of input span
* 0 (0.0, 0.00): ON/OFF action
ON/OFF action differential gap: RTD input:
0 (0.0, 0.00) to Input span (unit:
C)
(Varies with the setting of the decimal point
position. However, even if "3: Three decimal
places" is set, the maximum settable decimal
places
are
2.)
Voltage input: 0.00 to 100.00
of input span
b) Integral time (I):
0.0 to 3000.0 seconds
(0.0: Integral action OFF)
c) Derivative time (D): 0.0 to 3000.0 seconds
(0.0:
Derivative action OFF)
d) Control response parameter:
Slow, Medium and Fast (3-step selection)
Internally fixed to Fast in case of P and PD actions.
e) Output limiter high: Output limiter low to
105.0
f) Output limiter low:
5.0
to Output limiter high
g) Output change rate limiter (up/down):
0.0 to 100.0
/seconds of manipulated output
(0.0: Output change rate limiter OFF)
Up/Down individual setting
h) Manual reset:
100.0 to
100.0
i) Manual output:
Output limiter low to Output limiter high
j) Manipulated output value at STOP mode:
5.0 to
105.0
k) Derivative action: 0 (Measured value derivative),
1 (Deviation derivative)
l) Derivative gain:
0.1 to 10.0
m) Integral/Derivative time decimal point position:
1 (0.1 seconds setting)
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...