9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-30
PV low input cut-off
RKC communication
identifier
DP
Modbus
register address
ch1: 00DEH (222)
ch2: 00DFH (223)
PV low input cut-off is used with Square root extraction function. The measured value less than the PV low
input cut-off is ignored to prevent control disturbance caused by input variation at low measured value range.
Attribute:
R/W
When square root extraction is “0: Unused,” the PV low input cut-off will be RO.
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0.00 to 25.00 % of input span
Factory set value:
0.00
Related parameters:
Square root extraction (P. 9-49)
Function:
When input signal square root extraction is used for in flow control, etc., the square
root extraction result varies widely at the low measured value range. The measured
value less than the PV low input cut-off is ignored to compute control output in order
to prevent control disturbance caused by input variation at low measured value range.
100 %
70.7 %
50 %
Output
Input
100 %
50 %
25 %
When set value of the PV low input cut-off is 15 %
0 %
When set value of the
PV low input cut-off is
0 %
RS bias
(Cascade bias)
RKC communication
identifier
RB
Modbus
register address
ch1: 00E2H (226)
ch2: 00E3H (227)
RS bias adds bias to the Remote setting (RS) input value.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
Input span to +Input span
(Varies with the setting of the decimal point position. However, even if "3: Three
decimal places" is set, the maximum settable decimal places are 2.)
Factory set value:
0.00
Related parameters:
Remote/Local transfer (P. 9-16), SV select function (P. 9-83),
Remote SV function master channel module address (P. 9-87),
Remote SV function master channel selection (P. 9-88)
When the cascade control is selected, this is used as the cascade bias.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...