8. COMMUNICATION DATA LIST
IMS01T28-E4
8-7
Continued from the previous page.
No. Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
48
Reserved
00CE
00CF
206
207
49 PV
bias
PB CH1
CH2
00D2
00D3
210
211
7 R/W C
Input span to
Input span
Varies with the setting of the decimal
point position.
For the 1/1000 °C unit, the minimum
value is limited to “
99.999.”
0.00 (0.000)
50
PV digital filter
F1
CH1
CH2
00D6
00D7
214
215
7 R/W C 0.0 to 100.0 seconds
(0.0: Unused)
0.0
51 PV
ratio
PR CH1
CH2
00DA
00DB
218
219
7
R/W
C
0.500 to 1.500
1.000
52
PV low input cut-off
DP
CH1
CH2
00DE
00DF
222
223
7
R/W
C
0.00 to 25.00 % of Input span
If the Square root extraction corresponds
to “0: Unused,” set to RO (Only reading
data is possible).
0.00
53
RS (cascade) bias
RB
CH1
CH2
00E2
00E3
226
227
7 R/W C
Input span to
Input span
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
0.00
54
RS (cascade) digital
filter
F2 CH1
CH2
00E6
00E7
230
231
7 R/W C 0.0 to 100.0 seconds
(0.0: Unused)
0.0
55
RS (cascade) ratio
RR
CH1
CH2
00EA
00EB
234
235
7
R/W
C
0.001 to 9.999
1.000
56
Output distribution
selection
DV CH1
CH2
00EE
00EF
238
239
1 R/W C 0: Control output
1: Distribution output
0
57
Output distribution
bias
DW CH1
CH2
00F2
00F3
242
243
7 R/W C
100.0 to
100.0 %
0.0
58
Output distribution
ratio
DQ CH1
CH2
00F6
00F7
246
247
7 R/W C
9.999 to
9.999 1.000
59
Proportional cycle
time
T0 CH1
CH2
00FA
00FB
250
251
7
R/W
C
0.1 to 100.0 seconds
This item becomes RO (Only reading
data is possible) for the Voltage/Current
output specification.
This parameter is valid when “0: control
output” has been selected at No. 10
“Output assignment” (P. 8-9).
Relay contact
output: 20.0
Voltage pulse
output, Triac
output and
Open collector
output: 2.0
60
Minimum ON/OFF
time of proportioning
cycle
VI CH1
CH2
00FE
00FF
254
255
7
R/W
C
0 to 1000 ms
This item becomes RO (Only reading
data is possible) for the Voltage/Current
output specification.
0
61
Manual manipulated
output value
ON CH1
CH2
0102
0103
258
259
7 R/W C Output limiter low to
Output limiter high
0.0
62
Area soak time stop
function
RV CH1
CH2
0106
0107
262
263
1 R/W C 0: No function
1: Event 1
2: Event 2
3: Event 3
4: Event 4
0
63 Operation
mode
EI CH1
CH2
0142
0143
322
323
1 R/W C 0: Unused
1: Monitor
2: Monitor
Event function
3: Control
3
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...