11. SPECIFICATIONS
IMS01T28-E4
11-13
Transportation and Storage environment conditions:
Vibration:
Number of vibration
Hz
Level
Attenuation slope
dB/oct
(m/s
2
)
2
/Hz [g
2
/Hz]
*
3 0.048
(0.0005)
3 to 6
13.75
6 to 18
1.15
(0.012)
18 to 40
9.34
40 0.096
(0.001)
40 to 200
1.29
200 0.048
(0.0005)
The effective value of the acceleration is 5.8 m/s
2
[0.59 g*] within the number of
vibration.
* g = 9.806658 m/s
2
Shock:
Height 800 mm or less
Temperature:
25 to
70
C (At storage)
40 to
70
C (At transport)
Humidity:
Less than 5 to 95 %RH (Non condensing)
Absolute humidity: MAX.W.C 35 g/m
3
dry air at 101.3 kPa
Mounting and Structure
:
Mounting method:
DIN rail mounting or Panel mounting
When the module is mounted on the panel,
allow a minimum of 50 mm at the top and
bottom of the module to attach the module to
the
mainframe.
Mounting orientation: Datum plane
10
Case material:
PPE [Flame retardancy: UL94 V-1]
Panel sheet material:
Polyester
Weight:
Approx. 160 g
Standard
Safety standards:
UL:
UL61010-1
cUL: CAN/CSA-C22.2
No.61010-1
CE marking:
LVD:
EN61010-1
OVERVOLTAGE CATEGORY II,
POLLUTION DEGREE 2,
Class II (Reinforced insulation)
EMC: EN61326-1
RCM:
EN55011
The following standards do not apply to triac output type.
CE/UL/cUL/RCM
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...