9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-35
Minimum ON/OFF time of proportioning
cycle
RKC communication
identifier
VI
Modbus
register address
ch1: 00FEH (254)
ch2: 00FFH (255)
This is the minimum ON/OFF time of the time proportioning cycle.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0 to 1000 ms
Factory set value:
0
Related parameters:
Proportional cycle time (P. 9-34), Output assignment (P. 9-50)
Function:
The minimum ON/OFF time of the proportioning cycle is used to prevent output
ON or OFF when the output is greater than 0 % or less than 100 %. This is useful
when you wish to establish a minimum ON/OFF time to prolong the life of the
relay.
Example 1: Setting of Minimum ON/OFF time of proportioning cycle
Computed output
More than 0 % (Around 0 %)
Computed
output
ON
OFF
*
When a long minimum ON/OFF time is required for the relay, set a time longer than that time.
ON
OFF
Actual output
ON
OFF
Computed
output
ON
OFF
Actual output
Setting of
Minimum
ON/OFF time
ON
OFF
DO proportioning cycle time
(ON time)
*
Less than 100 % (Around 100 %)
Setting of
Minimum
ON/OFF time
ON
OFF
(OFF time)
DO proportioning cycle time
*
Example 2: Setting of Minimum ON/OFF time of proportioning cycle
Computed output
More than 0 % (Around 0 %)
Computed
output
ON
OFF
*
When a long minimum ON/OFF time is required for the relay, set a time longer than that time.
ON
OFF
Actual output
ON
OFF
Computed
output
ON
OFF
Actual output
Setting of
Minimum
ON/OFF time
ON
OFF
DO proportioning cycle time
(ON time)
*
Less than 100 % (Around 100 %)
Setting of
Minimum
ON/OFF time
ON
OFF
(OFF time)
DO proportioning cycle time
*
This item becomes RO for the Voltage/Current output specification.
Operation will not take place if “Proportional cycle time
Minimum ON/OFF time of
proportioning cycle.”
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...