8. COMMUNICATION DATA LIST
IMS01T28-E4
8-5
Continued from the previous page.
No. Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
22
Logic output
monitor 1
ED
CH1
0044 68 7
RO
M
RKC communication
Least significant digit:
Logic output 1
2nt digit: Logic output 2
3rd digit: Logic output 3
4th digit: Logic output 4
5th digit to Most significant digit:
Unused
Data 0: OFF
1: ON
Modbus
Bit data
Bit 0: Logic output 1
Bit 1: Logic output 2
Bit 2: Logic output 3
Bit 3: Logic output 4
Bit 4: Logic output 5
Bit 5: Logic output 6
Bit 6 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 63]
23
Logic output
monitor 2
EE CH1
7
RO
M
Least significant digit:
Logic output 5
2nt digit: Logic output 6
3th digit to Most significant digit:
Unused
Data 0: OFF
1: ON
24 PID/AT
transfer
G1 CH1
CH2
0061
0062
97
98
1 R/W C 0: PID control
1: Autotuning (AT)
When the Autotuning (AT) is finished, the
control will automatically returns to 0: PID
control.
0
25 Auto/Manual
transfer J1 CH1
CH2
0065
0066
101
102
1 R/W C 0: Auto mode
1: Manual mode
0
26 Remote/Local
transfer C1 CH1
CH2
0069
006A
105
106
1 R/W C 0: Local mode
1: Remote mode
When performing remote control by
Remote setting input and also performing
Cascade control, transfer to the Remote
mode.
0
27
RUN/STOP transfer
SR
CH1
006D
109
1
R/W
M
0: STOP (Control stop)
1: RUN (Control start)
0
28 Memory
area
transfer ZA CH1
CH2
006E
006F
110
111
7
R/W
C
1 to 8
1
29 Interlock
release
AR CH1
CH2
0072
0073
114
115
1 R/W C 0: Normal state
1: Interlock release execution
0
30
Event 1 set value
(EV1)
★
A1 CH1
CH2
0076
0077
118
119
7 R/W C Deviation action, Deviation action
between channels:
Input span to +Input span *
Process action, SV action:
Input scale low to Input scale
high*
MV action:
5.0 to +105.0 %
If the Event type corresponds to “0:
None,” set to RO (Only reading data is
possible).
If Event 4 corresponds to “9: Control
loop break alarm (LBA),” the Event 4 set
value becomes RO (Only reading data is
possible).
*
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
50.00
31
Event 2 set value
(EV2)
★
A2 CH1
CH2
007A
007B
122
123
7 R/W C
50.00
32
Event 3 set value
(EV3)
★
A3 CH1
CH2
007E
007F
126
127
7 R/W C
50.00
33
Event 4 set value
(EV4)
★
A4 CH1
CH2
0082
0083
130
131
7 R/W C
50.00
★
Parameters which can be used in multi-memory area function
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...