9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-34
Output distribution bias
RKC communication
identifier
DW
Modbus
register address
ch1: 00F2H (242)
ch2: 00F3H (243)
The bias which is added to the manipulated output value of the master channel that is distributed to slave
channels and output.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
100.0 to
100.0 %
Factory set value:
0.0
Related parameters:
Output distribution selection (P. 9-32), Output distribution ratio (P. 9-34),
Output distribution master channel module address (P. 9-89),
Output distribution master channel selection (P. 9-90)
Output distribution ratio
RKC communication
identifier
DQ
Modbus
register address
ch1: 00F6H (246)
ch2: 00F7H (247)
The ratio (magnification) which is applied to the manipulated output value of the master channel that is
distributed to slave channels and output.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
9.999 to
9.999
Factory set value:
1.000
Related parameters:
Output distribution selection (P. 9-32), Output distribution bias (P. 9-34),
Output distribution master channel module address (P. 9-89),
Output distribution master channel selection (P. 9-90)
Proportional cycle time
RKC communication
identifier
T0
Modbus
register address
ch1: 00FAH (250)
ch2: 00FBH (251)
Proportional cycle time is to set control cycle time for time based control output such as Voltage pulse for
SSR, Triac, Relay and Open-collector output.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0.1 to 100.0 seconds
Factory set value:
Relay
contact
output:
20.0
Voltage pulse output (V), Triac output (T) and Open-collector output (D): 2.0
Related parameters:
Output assignment (P. 9-50)
To set the Proportioning cycle, “0: Control output” must be set in the output assignment item.
This item becomes RO for the Voltage/Current output specification.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...