8. COMMUNICATION DATA LIST
IMS01T28-E4
8-6
Continued from the previous page.
No. Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
34
Control loop break
alarm (LBA) time
★
A5 CH1
CH2
0086
0087
134
135
7 R/W C 0 to 7200 seconds
(0: Unused)
480
35 LBA
deadband
★
N1
CH1
CH2
008A
008B
138
139
7 R/W C 0 (0.0, 0.00) to Input span
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
0.00
36
Set value (SV)
★
S1
CH1
CH2
008E
008F
142
143
7 R/W C Setting limiter low to
Setting limiter high
Varies with the setting of the decimal
point position. However, in case of
MODBUS single word, even if "3: Three
decimal places" is set, the maximum
settable decimal places are 2.
RTD input:
0.00 (0.000)
V input:
0.000
37 Proportional
band
★
P1 CH1
CH2
0092
0093
146
147
7 R/W C RTD input:
0 (0.0, 0.00) to Input span
(Unit:
C)
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
Voltage (V) input:
0.00 to 300.00 % of input span
0 (0.0, 0.00): ON/OFF action
30.00
38 Integral
time
★
I1
CH1
CH2
0096
0097
150
151
7 R/W C 0.0 to 3000.0 seconds
(0.0: PD action)
240.0
39 Derivative
time
★
D1
CH1
CH2
009A
009B
154
155
7 R/W C 0.0 to 3000.0 seconds
(0.0: PI action)
60.0
40
Control response
parameter
★
CA CH1
CH2
009E
009F
158
159
1 R/W C 0: Slow
1: Medium
2: Fast
[Internally fixed to Fast in case of P and
PD actions.]
0
41 Manual
reset
★
MR CH1
CH2
00B2
00B3
178
179
7 R/W C
100.0 to +100.0 %
If the Integral function is valid, set to RO
(Only reading data is possible).
When Integral time is zero, manual reset
value is added to the control output.
0.0
42
Setting change rate
limiter (up)
★
HH CH1
CH2
00B6
00B7
182
183
7 R/W C 0 (0.0, 0.00) to
Input span/unit time *
0 (0.0, 0.00): Unused
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
* Unit time: 60 seconds (factory set
value)
0.00
43
Setting change rate
limiter (down)
★
HL CH1
CH2
00BA
00BB
186
187
7 R/W C
0.00
44
Area soak time
★
TM
CH1
CH2
00BE
00BF
190
191
7 R/W C 0 minutes 00 seconds to 199 minutes
59 seconds:
RKC communication:
0:00 to 199:59 (min:sec)
Modbus:
0 to 11999 seconds
0 hours 00 minutes to 99 hours 59
minutes:
RKC communication:
0:00 to 99:59 (hrs:min)
Modbus:
0 to 5999 minutes
Data range of Area soak time can be
selected on the Soak time unit.
RKC
communication:
0:00
Modbus: 0
45
Link area number
★
LP CH1
CH2
00C2
00C3
194
195
7 R/W C 0 to 8
(0: No link)
0
46
Reserved
00C6
00C7
198
199
47
Reserved
00CA
00CB
202
203
★
Parameters which can be used in multi-memory area function
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...