11. SPECIFICATIONS
IMS01T28-E4
11-8
Multi-memory area function
Number of areas:
8
areas/channel
Stored parameters:
Set value (SV), Event function 1 to 4, LBA time, LBA deadband,
Proportional band, Integral time, Derivative time,
Control response parameter, Manual reset,
Setting change rate limiter (up), Setting change rate limiter (down),
Soak time setting, Link area number
Method of area transfer
:
Communication
function
Internal communication
Area soak time
Memory area link function
:
Link area number:
0 to 8 (0: No link)
Soak time: 0 minutes 00 seconds to 199 minutes 59 seconds or
0 hours 00 minutes to 99 hours 59 minutes
(Selectable)
Accuracy:
(0.5
of set value
0.25 seconds)
Area soak time stop function:
0 (No function)
1 to 4 (Event 1to Event 4)