8. COMMUNICATION DATA LIST
IMS01T28-E4
8-10
Continued from the previous page.
No. Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
12
Event 1 type
XA CH1
CH2
01A2
01A3
418
419
7 R/W
1
C 0: None
1: Deviation high
(Using SV monitor value) *
2: Deviation low
(Using SV monitor value) *
3: Deviation high/low
(Using SV monitor value) *
4: Band (Using SV monitor value) *
5: Process high *
6: Process low *
7: SV high
8: SV low
9: Unused
10: MV high *
11: MV low *
12: Unused
13: Unused
14: Deviation high (Using local SV) *
15: Deviation low (Using local SV) *
16: Deviation high/low
(Using local SV) *
17: Band (Using local SV) *
18: Deviation between channels high
*
19: Deviation between channels low *
20: Deviation between channels
high/low
*
21: Deviation between channels
band
*
* Event hold action is available.
Based on
model code
When not
specifying: 0
13
Event 1 channel setting FA
CH1
CH2
01A6
01A7
422
423
1 R/W
1
C 1: Channel 1
2: Channel 2
This function is valid when “Deviation
between channels” is selected.
1
14
Event 1 hold action
WA
CH1
CH2
01AA
01AB
426
427
1 R/W
1
C 0: OFF
1: Hold action ON (when power
turned on; when transferred from
STOP to RUN)
2: Re-hold action ON (when power
turned
on;
when transferred from
STOP to RUN; SV changed)
This function is valid when input value,
deviation or manipulated value action has
been selected.
In case of a deviation action, this function
is not available while in Remote mode
and while setting changing rate limiter is
working.
Based on
model code
When not
specifying: 0
15
Event 1 interlock
LF
CH1
CH2
01AE
01AF
430
431
1 R/W
1
C 0: Unused
1: Used
0
16
Event 1 differential gap HA
CH1
CH2
01B2
01B3
434
435
7 R/W
1
C
Deviation, Process, Set value, or
Deviation action between
channels:
0 (0.0, 0.00) to Input span
(Unit:
C)
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
MV: 0.0 to 110.0 %
: 1.00
: 1.0
17
Event 1 delay timer
TD
CH1
CH2
01B6
01B7
438
439
7 R/W
1
C
0 to 18000 seconds
0
1
During RUN (control), the attribute of Engineering setting data is RO. To configure Engineering setting data, the RUN/STOP switch must
be set to STOP (control stopped).
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...