9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-101
Output adjustment mode
RKC communication
identifier
bs
Modbus
register address
Used to select the output accuracy for Voltage/Current outputs.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0: Normal operation
1: Output adjustment 5 %
2: Output adjustment 100 %
Factory set value:
0
Related parameters:
Output adjustment value 5 % (P. 9-101), Output adjustment value 100 % (P. 9-102)
Function:
The output accuracy at the time of shipment (without output adjustment) is
3 % of
the span. Output adjustment improves the accuracy to
0.5 % of the span.
[Output adjustment procedure]
1.
Connect a multimeter or equivalent so that the output from the Z-TIO-G can be
measured.
2.
Set the Output adjustment mode to “1: Output adjustment 5 %.”
3.
Change the output adjustment 5 % data so that the output from the Z-TIO-G
becomes 5 %.
4.
Set the Output adjustment mode to “2: Output adjustment 100 %.”
5.
Change the output adjustment 100 % data so that the output from the Z-TIO-G
becomes 100 %.
This parameter is active when the control is stopped (STOP) and when the instrument has
Voltage/Current output.
Output adjustment 5 %
RKC communication
identifier
bt
Modbus
register address
This parameter is used to adjust the accuracy when the Voltage/Current output is 5 %.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0 to 10000
Factory set value:
2195
Related parameters:
Output adjustment mode (P. 9-101), Output adjustment 100 % (P. 9-102)
This parameter is active when control is stopped (STOP), when output type is Voltage/Current,
and when the Output adjustment mode is other than zero.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...