9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-57
Event 1 interlock
RKC communication
identifier
LF
Modbus
register address
ch1: 01AEH (430)
ch2: 01AFH (431)
Event 2 interlock
RKC communication
identifier
LG
Modbus
register address
ch1: 01CAH (458)
ch2: 01CBH (459)
Event 3 interlock
RKC communication
identifier
LH
Modbus
register address
ch1: 01E6H (486)
ch2: 01E7H (487)
Event 4 interlock
RKC communication
identifier
LI
Modbus
register address
ch1: 0202H (514)
ch2: 0203H (515)
Use to select the interlock function for the Event.
Attribute:
R/W
Digits:
1
digit
Number of data:
2 (Data of each channel)
Data range:
0: Unused
1: Used
Factory set value:
0
Related parameters:
Comprehensive event state (P. 9-4), Event state monitor (P. 9-8),
Event set value (P. 9-19), Event type (P. 9-52), Event differential gap (P. 9-58),
Event delay timer (P. 9-59), Force ON of Event action (P. 9-61)
Function:
The event interlock function is used to hold the event state even if the measured
value (PV) is out of the event area after its entry into the area once.
Example: When the event interlock function is used for deviation high
Event set value
Set value (SV)
Event status
OFF
ON
Measured value (PV)
Time
Event interlock
Deviation
Measured value (PV)
[Without Event hold action]
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...