8. COMMUNICATION DATA LIST
IMS01T28-E4
8-3
8.2 Normal Setting Data
No. Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
1
Model code
ID
32
RO
M
Model code (character)
2
ROM version
VR
8
RO
M
ROM version
3
Measured value (PV)
M1
CH1
CH2
0000
0001
0
1
7 RO C Input scale low to Input scale high
Varies with the setting of the decimal
point position. However, in case of
MODBUS single word, even if "3: Three
decimal places" is set, the maximum
settable decimal places are 2.
4
Comprehensive event
state
AJ CH1
CH2
0004
0005
4
5
7 RO C
RKC communication
Least significant digit: Event 1
2nd digit:
Event 2
3rd digit:
Event 3
4th digit:
Event 4
5th digit:
Unused
6th digit:
Unused
Most significant digit: Burnout
Data 0: OFF
1: ON
Modbus
Bit data
Bit 0: Event 1
Bit 1: Event 2
Bit 2: Event 3
Bit 3: Event 4
Bit 4: Unused
Bit 5: Unused
Bit 6: Burnout
Bit 7 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 79]
5
Operation mode state
monitor
L0 CH1
CH2
0008
0009
8
9
7 RO C
RKC communication
Least significant digit:
Control
STOP
2nd digit: Control RUN
3rd digit: Manual mode
4th digit: Remote mode
5th digit to Most significant digit:
Unused
Data 0: OFF
1: ON
Modbus
Bit data
Bit 0: Control STOP
Bit 1: Control RUN
Bit 2: Manual mode
Bit 3: Remote mode
Bit 4 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 15]
6 Error
code
ER CH1 000C
12
7 RO M
RKC communication
1: Adjustment data error
2: Data back-up error
4: A/D conversion error
32: Logic output data error
If two or more errors occur
simultaneously, the total summation of
these error codes is displayed.
Modbus
Bit data
Bit 0: Adjustment data error
Bit 1: Data back-up error
Bit 2: A/D conversion error
Bit 3: Unused
Bit 4: Unused
Bit 5: Logic output data error
Bit 6 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 63]
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...