9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-37
Operation mode
RKC communication
identifier
EI
Modbus
register address
ch1: 0142H (322)
ch2: 0143H (323)
This mode is used to select “unused,” “monitor,” “monitor
event function,” or “control” for each channel.
Attribute:
R/W
Digits:
1
digit
Number of data:
2 (Data of each channel)
Data range:
0: Unused (Neither monitor nor control is performed)
1: Monitor (Only data monitor is performed)
2:
Monitor
Event function
(Data monitor and event action [including LBA] are performed)
3:
Control
(Control is performed)
Factory set value:
3
Related parameters:
Operation mode state monitor (P. 9-5), RUN/STOP transfer (P. 9-16),
Control RUN/STOP holding setting (P. 9-94)
Instrument action states in each operation mode from the RUN/STOP state:
Operation Mode
Unused Monitor
Monitor
Event
function
Control
RUN
state
Monitor (measured value)
“0” is displayed
Measured value
Event action
Event function disabled
1
Event function enabled
Output terminal (when
control output is selected)
2
Output of
5 %
Manipulated output value at STOP mode
Control output value
Output terminal (when
logic output is selected)
3
Depends on logic output result
Output terminal (when
FAIL output is selected)
4
Depends on FAIL result
STOP
state
Monitor (measured value)
“0” is displayed
Measured value
Event action
Event function disabled
1
Output terminal (when
control output is selected)
2
Output of
5 %
Manipulated output value at STOP mode
Output terminal (when
logic output is selected)
3
Logic output result: OFF
Output terminal (when
FAIL output is selected)
4
Depends on FAIL result
1
If this instrument action state occurs when event interlock is ON, the interlock will be canceled.
2
When the output type is relay contact output, voltage pulse output, triac output, or open collector output, the output is limited to the
range 0 to 100 %.
3
When the output type is voltage output or current output, logic output is disabled.
4
When the output type is voltage output or current output, FAIL output is disabled.
Instrument action states depending on the operation mode and RUN/STOP switching:
Operation Mode
RUN/STOP
State
Monitor
Event function state
STOP
↓
RUN
Event function
*
Action according to the selection in “Event Hold Action” (P. 9-55).
Control state
Event function
*
Action according to the selection in “Event Hold Action” (P. 9-55).
Control
Action according to the settings in “Control RUN/STOP Hold
Setting” (P. 9-94), “Hot/Cold Start” (P. 9-63), and “Start
Determination Point” (P. 9-64).
Unused or Monitor
↓
Monitor
Event function
RUN state
Event function
*
Action according to the selection in “Event Hold Action” (P. 9-55).
Unused or Monitor
↓
Control
Event function
*
Action according to the selection in “Event Hold Action” (P. 9-55).
Control
Same action as when power is turned on.
Monitor
Event function
↓
Control
Control
Same action as when power is turned on.
*
Excluding the SV high, SV low, and control loop break alarm (LBA).
Link Z-TIO module and Z-DIO module to switch Operation mode by using Digital input (DI).
For details, refer to
Address of interacting modules (P. 9-91), Selection switch of interacting
modules (P. 9-92)
and
SRZ Instruction Manual (IMS01T04-E
)
.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...