9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-71
Manipulated output value at input error
RKC communication
identifier
OE
Modbus
register address
ch1: 0256H (598)
ch2: 0257H (599)
When the measured value reaches Input error determination point and Action at input error is set to “1:
Manipulated output value at input error,” this manipulated value is output.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
105.0 to
105.0 %
Factory set value:
0.0
Related parameters:
Action (high/low) at input error (P. 9-70), Output limiter high/low (P. 9-73)
The actual output value becomes the value restricted by the output limiter.
Manipulated output value at STOP mode
RKC communication
identifier
OF
Modbus
register address
ch1: 025AH (602)
ch2: 025BH (603)
Manipulated output value to be output at STOP (control stop).
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
5.0 to
105.0 %
Factory set value:
5.0
Related parameters:
RUN/STOP transfer (P. 9-16), Operation mode (P. 9-37)
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...