8. COMMUNICATION DATA LIST
IMS01T28-E4
8-17
Continued from the previous page.
No. Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
51 Derivative
gain
DG CH1
CH2
0242
0243
578
579
7 R/W
* C 0.1 to 10.0
6.0
52
ON/OFF action
differential gap
(upper)
IV CH1
CH2
0246
0247
582
583
7 R/W
* C RTD input:
0 (0.0, 0.00) to Input span
(Unit:
C)
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
Voltage (V) input:
0.00 to 100.00 % of input span
RTD input:
1.00
V input:
1.00
53
ON/OFF action
differential gap
(lower)
IW CH1
CH2
024A
024B
586
587
7 R/W
* C
RTD input:
1.00
V input:
1.00
54
Action (high) at input
error
WH CH1
CH2
024E
024F
590
591
1 R/W
* C 0: Normal control
1: Manipulated output value at
input
error
0
55
Action (low) at input
error
WL CH1
CH2
0252
0253
594
595
1 R/W
* C
0
56
Manipulated output
value at input error
OE CH1
CH2
0256
0257
598
599
7 R/W
* C
105.0 to
105.0 %
Actual output values become those
restricted by the output limiter.
0.0
57
Manipulated output
value at STOP mode
OF CH1
CH2
025A
025B
602
603
7 R/W
* C
5.0 to
105.0 %
5.0
58
Output change rate
limiter (up)
PH CH1
CH2
0262
0263
610
611
7 R/W
* C 0.0 to 100.0 % of manipulated
output/seconds
(0.0: OFF)
0.0
59
Output change rate
limiter (down)
PL CH1
CH2
0266
0267
614
615
7 R/W
* C
0.0
60
Output limiter high
OH
CH1
CH2
026A
026B
618
619
7
R/W
C
Output limiter low to 105.0 %
105.0
61
Output limiter low
OL
CH1
CH2
026E
026F
622
623
7 R/W C
5.0 % to Output limiter high
5.0
62
AT bias
GB
CH1
CH2
0282
0283
642
643
7 R/W
* C
Input span to +Input span
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
When the AT point exceeds the setting
range, high (or low) limit of the setting
range becomes the AT point.
0.00
63
AT cycles
G3
CH1
CH2
0286
0287
646
647
1 R/W
* C 0: 1.5 cycles
1: 2.0 cycles
2: 2.5 cycles
3: 3.0 cycles
1
64
Output value with AT
turned on
OP CH1
CH2
028A
028B
650
651
7 R/W
* C Output value with AT turned off to
105.0 %
Actual output values become those
restricted by the output limiter.
105.0
65
Output value with AT
turned off
OQ CH1
CH2
028E
028F
654
655
7 R/W
* C
105.0 % to Output value with AT
turned on
Actual output values become those
restricted by the output limiter.
105.0
66
AT differential gap
time
GH CH1
CH2
0292
0293
658
659
7 R/W * C
0.0 to 50.0 seconds
10.0
67
Proportional band
adjusting factor
KC CH1
CH2
0296
0297
662
663
7 R/W * C
0.01 to 10.00 times
1.00
68
Integral time
adjusting factor
KD CH1
CH2
029A
029B
666
667
7 R/W * C
0.01 to 10.00 times
1.00
69
Derivative time
adjusting factor
KE CH1
CH2
029E
029F
670
671
7 R/W * C
0.01 to 10.00 times
1.00
* During RUN (control), the attribute of Engineering setting data is RO. To configure Engineering setting data, the RUN/STOP switch must
be set to STOP (control stopped).
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...