9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-24
Control response parameter
RKC communication
identifier
CA
Modbus
register address
ch1: 009EH (158)
ch2: 009FH (159)
The control response for the Set value (SV) change can be selected among Slow, Medium, and Fast.
Attribute:
R/W
Digits:
1
digit
Number of data:
2 (Data of each channel)
Data range:
0: Slow
1:
Medium
2:
Fast
Factory set value:
0
Related parameters:
Control action (P. 9-66)
Function:
The control response for the Set value (SV) change can be selected among Slow,
Medium, and Fast. If a fast response is required, Fast is chosen. Fast may cause
overshoot. If overshoot is critical, Slow is chosen.
Fast
Selected when rise time needs to be shortened (operation needs to started fast).
However in this case, slight overshooting may not be avoided.
Medium
Middle between “Fast” and “Slow.”
Overshooting when set to “Medium” becomes less than that when set to “Fast.”
Slow
Selected when no overshooting is allowed.
Used when material may be deteriorated if the temperature becomes higher that the
set value.
Measured value (PV)
Set value (SV)
Change
Set value (SV) change point
Time
Fast
Medium
Slow
Set value (SV)
When the P or PD action is selected, this setting becomes invalid.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...