9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-43
When the Input scale high/low parameter is changed
When the high limit or low limit of the input scale is changed, the settings in the following table will be
changed. Reset the settings to the values that you wish to use.
Input scale high (RKC communication identifier: XV, Modbus address: 0182H to 0183H)
Input scale low (RKC communication identifier: XW, Modbus address: 0186H to 0187H)
Items that are initialized:
Data type
Items
Default value
Engineering
Input error determination point (high)
Input range high
(5 % of Input span)
setting data
Input error determination point (low)
Input range low
(5 % of Input span)
Setting limiter high
Input scale high
Setting limiter low
Input scale low
Items processed by limiter processing:
Data type
Items
Engineering
Event 1 differential gap
1
ON/OFF action differential gap (upper)
2
setting data
Event 2 differential gap
1
ON/OFF action differential gap (lower)
2
Event 3 differential gap
1
AT
bias
Event 4 differential gap
1
Proportional band limiter (high)
2
Start determination point
Proportional band limiter (low)
2
Normal setting
Event 1 set value (EV1)
1
Proportional
band
2
data
Event 2 set value (EV2)
1
Setting change rate limiter (up)
Event 3 set value (EV3)
1
Setting change rate limiter (down)
Event 4 set value (EV4)
1
PV
bias
LBA deadband
RS bias
Set value (SV)
1
Only for deviation, process, or set value.
2.
Only for RTD input.
When the Integral/Derivative time decimal point position parameter is changed
When the Integral/Derivative time decimal point position is changed (RKC communication identifier: PK,
Modbus address: 0236H to 0237H), the decimal point positions of the settings in the following table are
automatically converted. However, in some cases, the change of decimal point position may also change the
set value. Where this occurs, reset the value to the value that you wish to use.
Data type
Items
Engineering
Integral time limiter (high)
Derivative time limiter (high)
setting data
Integral time limiter (low)
Derivative time limiter (low)
Normal setting
Integral time
Derivative time
data
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...