9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-80
Derivative time limiter (high)
RKC communication
identifier
D6
Modbus
register address
ch1: 02BEH (702)
ch2: 02BFH (703)
Derivative time limiter (low)
RKC communication
identifier
D7
Modbus
register address
ch1: 02C2H (706)
ch2: 02C3H (707)
Derivative time limiter (high): Use to set the high limit value of Derivative time.
Derivative time limiter (low): Use to set the low limit value of Derivative time.
(However, Derivative time limiter (high)
Derivative time limiter (low))
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0.00 to 3000.0 seconds (0.0: PI action)
Factory set value:
Derivative time limiter (high): 3000.0
Derivative time limiter (low): 0.0
Related parameters:
PID/AT transfer (P. 9-13), Derivative time (P. 9-23),
Integral/Derivative time decimal point position
(P. 9-68)
Function:
The Derivative time range is restricted while the Autotuning (AT) function is being
executed.
If the Autotuning (AT) function is executed when the Derivative time limiter (high) is set at “0.0,”
P and I values suitable to PI control are computed.
Setting change rate limiter unit time
RKC communication
identifier
HU
Modbus
register address
ch1: 031EH (798)
ch2: 031FH (799)
Set the time unit for Setting change rate limiter (UP/DOWN).
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
1 to 3600 seconds
Factory set value:
60
Related parameters:
Setting change rate limiter (up) (P. 9-26), Setting change rate limiter (down) (P. 9-26)
Soak time unit
RKC communication
identifier
RU
Modbus
register address
ch1: 0322H (802)
ch2: 0323H (803)
Use to select the time unit for Area soak time.
Attribute:
R/W
Digits:
1
digit
Number of data:
2 (Data of each channel)
Data range:
0:
0 hours 00 minutes to 99 hours 59 minutes
RKC communication: 0 hours 00 minutes to 99 hours 59 minutes
Modbus:
0 to 5999 minutes
1: 0 minutes 00 seconds to 199 minutes 59 seconds
RKC communication: 0 minutes 00 seconds to 199 minutes 59 seconds
Modbus:
0 to 11999 seconds
Factory set value:
RKC
communication:
1
Modbus: 1
Related parameters:
Memory area soak time monitor (P. 9-10), Area soak time (P. 9-27)
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...