9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-55
Event 1 hold action
RKC communication
identifier
WA
Modbus
register address
ch1: 01AAH (426)
ch2: 01ABH (427)
Event 2 hold action
RKC communication
identifier
WB
Modbus
register address
ch1: 01C6H (454)
ch2: 01C7H (455)
Event 3 hold action
RKC communication
identifier
WC
Modbus
register address
ch1: 01E2H (482)
ch2: 01E3H (483)
Event 4 hold action
RKC communication
identifier
WD
Modbus
register address
ch1: 01FEH (510)
ch2: 01FFH (511)
Use to set an event hold action for the Event.
Attribute:
R/W
Digits:
1
digit
Number of data:
2 (Data of each channel)
Data range:
0 to 2
Data range
Factory set value
0: OFF
1: Hold action ON (Only hold action)
Validate the hold action when the power is turned on.
Validate the hold action when transferred from STOP (control
STOP) to RUN (control RUN).
2: Re-hold action ON (hold and re-hold actions)
Validate the hold action when the power is turned on.
Validate the hold action when transferred from STOP (control
STOP) to RUN (control RUN).
Validate the re-hold action when the Set value (SV) is
changed.
However, if the rate of setting change limiter is set to any
function other than “OFF (Unused)” or in the remote mode,
the re-hold action becomes invalid.
Based on model code
When not specifying: 0
When high alarm with Hold/Re-hold action is used for Event function,
alarm does not turn on while Hold action is in operation. Use in
combination with a high alarm without Hold action in order to prevent
overheating which may occur by failure of control devices, such as
welding of relays.
The hold action is effective when Process, Deviation, or Manipulated output
value action is selected for the Event type.
Related parameters:
Comprehensive event state (P. 9-4), Event state monitor (P. 9-8),
Event set value (P. 9-19), Event type (P. 9-52), Event interlock (P. 9-57),
Event differential gap (P. 9-58), Event delay timer (P. 9-59)
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...