9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-9
Output state monitor
RKC communication
identifier
Q1
Modbus
register address
0039H (57)
ON/OFF state of output (OUT1 and OUT2) is expressed as a bit image in decimal number.
Attribute:
RO
Digits:
7
digits
Number of data:
1 (Data of each module)
Data range:
RKC communication:
ASCII code data
The output state is assigned as a digit image in ASCII code data of 7 digits.
ASCII code data of 7 digits:
Most significant digit ············ Least significant digit
Data:
0: OFF 1: ON
Modbus:
0 to 3 (bit data)
The output state is assigned as a bit image in binary numbers.
Bit image: 0000000000000000
Bit 15 ······················· Bit 0
Bit data: 0: OFF
1: ON
Factory set value:
Related parameters:
Output assignment (P. 9-50)
When the output type is control output, this is only effective when time proportional output is
used.
Bit 0:
OUT1
Bit 1:
OUT2
Bit 2 to Bit 15: Unused
Least significant digit: OUT1
2nd digit:
OUT2
3rd digit to Most significant digit:
Unused
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...