7. MODBUS
IMS01T28-E4
7-17
7.5 How to Use Data Mapping
When this communication method is used, 16 types of data (mapping data) can be specified as desired for
the Z-TIO-G module, and read/write can be performed continuously.
Data range
Register address to specify mapping data
1000H to 100FH
Register address to actually read/write data
1500H to 150FH
Register address of data which can be mapped
Refer to
8.2 Normal Setting Data (P.8-3)
and
8.3 Engineering Setting
Data (P. 8-9).
For the data mapping address list, refer to the
8.5 Data Mapping Address (P. 8-24)
.
[Example]
Mapping the CH1 data “Measured value (PV), Manipulated output value (MV) monitor, Event 1
state monitor, Event 2 state monitor” of a Z-TIO module to register addresses 1500H to 1503H.
For data mapping
Mapping data
Name
Register address
Name
Register address (CH1)
HEX DEC
HEX DEC
Register address setting 1
Read/write address: 1500H
1000 4096
Measured value (PV)
0000 0
Register address setting 2
Read/write address: 1501H
1001 4097
Manipulated output value (MV)
monitor
000D 13
Register address setting 3
Read/write address: 1502H
1002 4098
Event 1 state monitor
0025 37
Register address setting 4
Read/write address: 1503H
1003 4099
Event 2 state monitor
0029 41
1.
The register address, “0000H” of the Measured value (PV) to be mapped is written to register address
setting 1 (1000H).
2.
The register address, “000DH” of the Manipulated output value (MV) monitor to be mapped is written
to register address setting 2 (1001H).
3.
The register address, “0025H” of the Event 1 state monitor to be mapped is written to register address
setting 3 (1002H).
4.
The register address, “0029H” of the Event 2 state monitor to be mapped is written to register address
setting 4 (1003H).
5.
The assignment of the register addresses from 1500H to 1503H from/to which data is actually
read/written becomes as follows.
Register address
Name
HEX DEC
1500 5376
Measured
value
(PV)
1501
5377
Manipulated output value (MV) monitor
1502
5378
Event 1 state monitor
1503
5379
Event 2 state monitor
Write
High-speed communication is
performed by reading or writing data in
the consecutive register addresses from
1500H to 1503H.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...