9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-79
Proportional band limiter (high)
RKC communication
identifier
P6
Modbus
register address
ch1: 02AEH (686)
ch2: 02AFH (687)
Proportional band limiter (low)
RKC communication
identifier
P7
Modbus
register address
ch1: 02B2H (690)
ch2: 02B3H (691)
Proportional band limiter (high): Use to set the high limit value of Proportional band.
Proportional band limiter (low): Use to set the low limit value of Proportional band.
(However, Proportional band limiter (high)
Proportional band limiter (low))
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
RTD input:
0 (0.0, 0.00) to Input span (Unit:
C)
(Varies with the setting of the decimal point position.
However, even if "3: Three decimal places" is set, the maximum
settable decimal places are 2.)
Voltage (V) input: 0.00 to 300.00 % of input span
0 (0.0, 0.00): ON/OFF action
Factory set value:
Proportional band limiter (high): RTD input: Input
span
Voltage (V) input: 300.00
Proportional band limiter (low):
RTD input:
0.00
Voltage (V) input: 0.00
Related parameters:
PID/AT transfer (P. 9-13), Proportional band (P. 9-22),
Decimal point position
(P. 9-46)
Function:
The Proportional band range is restricted while the Autotuning (AT) function is
being executed.
Integral time limiter (high)
RKC communication
identifier
I6
Modbus
register address
ch1: 02B6H (694)
ch2: 02B7H (695)
Integral time limiter (low)
RKC communication
identifier
I7
Modbus
register address
ch1: 02BAH (698)
ch2: 02BBH (699)
Integral time limiter (high): Use to set the high limit value of Integral time.
Integral time limiter (low): Use to set the low limit value of Integral time.
(However, Integral time limiter (high)
Integral time limiter (low))
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0.0 to 3000.0 seconds (0.0: PD action)
Factory set value:
Integral time limiter (high): 3000.0
Integral time limiter (low): 0.0
Related parameters:
PID/AT transfer (P. 9-13), Integral time (P. 9-23),
Integral/Derivative time decimal point position
(P. 9-68)
Function:
The Integral time range is restricted while the Autotuning (AT) function is being
executed.
If the Autotuning (AT) function is executed when the Integral time limiter (high) is set at “0.0,” P
and D values suitable to PD control are computed.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...