3. COMMUNICATION SETTINGS
3-4
IMS01T28-E4
3.2 Protocol Selections and Communication Speed Setting
Use the DIP switch on the right side of module to select communication speed, data bit, configuration and
protocol. The data changes become valid when the power is turned on again or when changed to
RUN/STOP.
When two or more Z-TIO-G modules are connected on the same communication line, the DIP
switch settings (switch 1 to 8) of all modules must be the same. Otherwise the module may
fail or malfunction.
DIP switch
ON
OFF
1
2
3
4
5 6
7
8
ON
Module
mainframe
Right side view
Z-TIO-G module
1 2
Communication
speed
OFF OFF
4800 bps
ON OFF
9600 bps
OFF ON
19200 bps
ON ON
38400 bps
Factory set value: 19200 bps
3
4
5
Data bit configuration
OFF OFF OFF
Data 7-bit, without parity, Stop 1-bit
*
OFF ON OFF
Data 7-bit, Even parity, Stop 1-bit
*
ON ON OFF
Data 7-bit, Odd parity, Stop 1-bit
*
OFF OFF ON
Data 8-bit, without parity, Stop 1-bit
OFF ON ON
Data 8-bit, Even parity, Stop 1-bit
ON ON ON
Data 8-bit, Odd parity, Stop 1-bit
ON OFF OFF
Do not set this one
ON OFF
ON
Factory set value: Data 8-bit, without parity, stop 1-bit
*
When the Modbus communication protocol is selected, this setting becomes invalid.
6 Protocol
OFF
RKC communication
ON
Modbus
Factory set value: RKC communication
Switch No. 7 and 8 must be always OFF. Do not set to ON.
Setting range
of Modbus
Setting range of
RKC communication
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...