9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-51
Energized/De-energized
(Logic output selection function)
RKC communication
identifier
NA
Modbus
register address
ch1: 019EH (414)
ch2: 019FH (415)
Energized/De-energized can be selected for any of outputs 1 (OUT1) and 2 (OUT2) that have an output
function (logic output result) assigned.
Attribute:
R/W
Digits:
1
digit
Number of data:
2 (Data of each channel)
Data range:
0: Energized
1: De-energized
Factory set value:
0
Related parameters:
Output assignment (P. 9-50), Event type (P. 9-52),
Communication switch for logic (P. 9-38)
Function:
Action of Energized/De-energized
Energized/De-energized
setting
Output state of OUT1 and OUT2
Non-event state
Event state
Energized
Event output OFF
Event output ON
De-energized
Event output ON
Event output OFF
Example: Relay contact output
Energized:
Relay contact is closed under the event or alarm state.
De-energized: Relay contact opens under the event or alarm state.
Diagram for explaining operation (At power-ON)
Energized
Non-event state
Event state
De-
energized
Non-event state
Event state
In the following cases, the selection is fixed at de-energized.
An output that has an output assignment of “0: Control output”
FAIL alarm (normal: contacts closed, error: contacts open)
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...