9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-25
Manual reset
RKC communication
identifier
MR
Modbus
register address
ch1: 00B2H (178)
ch2: 00B3H (179)
In order to eliminate the offset occurring in Proportional (P) control, the manipulated output value is
manually corrected.
When the Manual reset is set to the plus (+) side:
The manipulated output value under the stable condition increases by the Manual reset value.
When the Manual reset is set to the minus (
) side:
The manipulated output value under the stable condition decreases by the Manual reset value.
Attribute:
R/W
When the integral function is enabled, the Manual reset is RO.
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
100.0 to +100.0 %
Factory set value:
0.0
Related parameters:
Integral time (P. 9-23)
Function:
This is the function used to manually correct the offset when in Proportional (P)
control or PD control.
Offset means the deviation of the actual when the manipulated output value
becomes stabilized (stable state). If the manual reset value varies, the manipulated
output value also changes.
Set value
(SV)
Offset
Measured
value (PV)
Temperature
Time
Measured
value (PV)
Offset
Manual reset is set.
To enable the Manual reset function, either Integral time must be set to zero.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...