8. COMMUNICATION DATA LIST
IMS01T28-E4
8-18
Continued from the previous page.
No. Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
70 Proportional
band
limiter (high)
P6 CH1
CH2
02AE
02AF
686
687
7 R/W
* C RTD input:
0 (0.0, 0.00) to Input span
(Unit:
C)
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
Voltage (V) input:
0.00 to 300.00 % of input span
0 (0.0, 0.00): ON/OFF action
RTD input:
Input span
V input:
300.00
71 Proportional
band
limiter (low)
P7 CH1
CH2
02B2
02B3
690
691
7 R/W
* C
RTD input:
0.00
V input:
0.00
72 Integral time limiter
(high)
I6 CH1
CH2
02B6
02B7
694
695
7 R/W
* C 0.0 to 3000.0 seconds
(0.0: PD action)
3000.0
73 Integral time limiter
(low)
I7 CH1
CH2
02BA
02BB
698
699
7 R/W
* C 0.0 to 3000.0 seconds
(0.0: PD action)
0.0
74 Derivative time limiter
(high)
D6 CH1
CH2
02BE
02BF
702
703
7 R/W
* C 0.0 to 3000.0 seconds
(0.0: PI action)
3000.0
75 Derivative time limiter
(low)
D7 CH1
CH2
02C2
02C3
706
707
7 R/W
* C 0.0 to 3000.0 seconds
(0.0: PI action)
0.0
76 Setting change rate
limiter unit time
HU CH1
CH2
031E
031F
798
799
7 R/W * C
1 to 3600 seconds
60
77 Soak time unit
RU
CH1
CH2
0322
0323
802
803
1 R/W
* C
RKC communication
0: 0:00 to 99:59 (hrs:min)
[0 hours 00 minutes to 99 hours
59
minutes]
1: 0:00 to 199:59 (min:sec)
[0 minutes 00 seconds to 199
minutes 59 seconds]
Modbus
0: 0 to 5999 minutes
[0 hours 00 minutes to
99 hours 59 minutes]
1: 0 to 11999 seconds
[0 minutes 00 seconds to
199 minutes 59 seconds]
Set the data range of Memory area soak
time monitor and Area soak time.
1
78 Setting limiter high
SH
CH1
CH2
0326
0327
806
807
7 R/W
* C Setting limiter low to Input scale
high
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
Input scale
high
79 Setting limiter low
SL
CH1
CH2
032A
032B
810
811
7 R/W
* C Input scale low to Setting limiter
high
Varies with the setting of the decimal
point position. However, even if "3:
Three decimal places" is set, the
maximum settable decimal places are 2.
Input scale
low
80 PV transfer function
TS
CH1
CH2
032E
032F
814
815
1 R/W
* C 0: Unused
1: Used
0
81 Operation
mode
assignment 1
(Logic output selection
function)
Logic output 1 to 4
EA CH1
CH2
0332
0333
818
819
7 R/W
* C 0: No assignment
1: Operation mode
(Monitor/Control)
2: Operation mode
(Monitor
Event function/Control)
3: Auto/Manual
4: Remote/Local
5: Unused (Do not set this one.)
0
* During RUN (control), the attribute of Engineering setting data is RO. To configure Engineering setting data, the RUN/STOP switch must
be set to STOP (control stopped).
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...