9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-31
RS digital filter
(Cascade digital filter)
RKC communication
identifier
F2
Modbus
register address
ch1: 00E6H (230)
ch2: 00E7H (231)
This item is the time of the first-order lag filter to eliminate noise against the Remote setting input.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0.0 to 100.0 seconds
(0.0:
Unused)
Factory set value:
0.0
Related parameters:
Remote/Local transfer (P. 9-16), SV select function (P. 9-83),
Remote SV function master channel module address (P. 9-87),
Remote SV function master channel selection (P. 9-88)
When the cascade control is selected, this is used as the cascade digital filter.
RS ratio
(Cascade ratio)
RKC communication
identifier
RR
Modbus
register address
ch1: 00EAH (234)
ch2: 00EBH (235)
RS ratio is a multiplier to be applied to the Remote setting (RS) input value.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0.001 to 9.999
Factory set value:
1.000
Related parameters:
Remote/Local transfer (P. 9-16), SV select function (P. 9-83),
Remote SV function master channel module address (P. 9-87),
Remote SV function master channel selection (P. 9-88)
When the cascade control is selected, this is used as the cascade ratio.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...