9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-63
Hot/Cold start
RKC communication
identifier
XN
Modbus
register address
ch1: 0222H (546)
ch2: 0223H (547)
Use to select the start mode at power recovery.
Attribute:
R/W
Digits:
1
digit
Number of data:
2 (Data of each channel)
Data range:
0: Hot start 1
1: Hot start 2
2: Cold
start
Factory set value:
0
Related parameters:
RUN/STOP transfer (P. 9-16), Operation mode (P. 9-37),
Start determination point (P. 9-64)
Function:
The operation of this instrument is not affected by a power failure of 4 ms or less.
The control start mode at power recovery after more than 4 ms power failure can be
selected as follows.
Action when power
failure recovers
Operation mode when power
failure recovers
Output value when power
failure recovers
Hot start 1
Same as that before power failure
Near the output value before power failure occurs.
Hot start 2
Same as that before power failure
Auto mode
Value as a result of control
computation
2
Manual mode
Output limiter low
Cold start
Manual
Output limiter low
1
Even when control is started by switching from STOP to RUN with the operation mode set to “Control,” operation will take place in the
start mode selected with Hot/Cold start.
2
The result of control computation varies with the control response parameter.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...