9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-36
Manual manipulated output value
RKC communication
identifier
ON
Modbus
register address
ch1: 0102H (258)
ch2: 0103H (259)
Use to set the output value in the Manual control.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
Output limiter low to Output limiter high
Factory set value:
0.0
Related parameters:
Output limiter high/low (P. 9-73)
The output of the ON/OFF action in the Manual mode is as follows.
・
When Manual manipulated output value
Output limiter (low) (or 0.0 % or less)
→
Output limiter (low)
・
When Manual manipulated output value
Output limiter (low) (or 0.0 % or less)
→
Output limiter (high)
Area soak time stop function
RKC communication
identifier
RV
Modbus
register address
ch1: 0106H (262)
ch2: 0107H (263)
Select the event for which the Area soak time is to be stopped when an event state occurs.
Attribute:
R/W
Digits:
1
digit
Number of data:
2 (Data of each channel)
Data range:
0: No function
3: Event 3
1: Event 1
4: Event 4
2:
Event
2
Factory set value:
0
Related parameters:
Area soak time (P. 9-27)
Function:
The Area soak time stop function stops the Area soak time count when an event
state occurs at the specified event output during soak operation. When the event
state is cleared, the area soak time count stop is canceled and soak operation
resumes from the state immediately prior to the stop.
Measured value (PV)
Set value (SV) of
Memory area 1
Area soak time of Memory area 1: 10 minutes
Area soak time stop function:
1 (Event 1)
Time
Present set value
(SV)
Event 1 state
occurs
Soak operation
(3 minutes)
Area soak time
stop
(2 minutes)
Event 1 state
cleared
Soak operation resumes
(Remaining operation time is
7 minutes)
Example:
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...