9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-32
Output distribution selection
RKC communication
identifier
DV
Modbus
register address
ch1: 00EEH (238)
ch2: 00EFH (239)
Select whether or not the manipulated output value of the specified master channel is output from slave
channels.
Attribute:
R/W
Digits:
1
digit
Number of data:
2 (Data of each channel)
Data range:
0: Control output (master channel)
1: Distribution output (slave channel)
Factory set value:
0
Related parameters:
Output distribution bias (P. 9-34), Output distribution ratio (P. 9-34),
Output distribution master channel module address (P. 9-89),
Output distribution master channel selection (P. 9-90)
Function:
The output distribution function outputs the manipulated output value computed for
the master channel as a manipulated output value from slave channels. Bias and
ratio computations can also be applied to the manipulated output value computed for
the master channel before it is output from the slave channels.
Number of output distribution channels: 187 channels maximum
(excluding the master channel)
[When Z-DIO module: 16 modules, Z-TIO module 4CH type: 15 modules]
Master channel
Z-TIO module
Sensor input
Setting change rate limiter
PID computation
Output limiter
Output
Capture the output value
Output distribution bias
Output limiter
Output
Manipulated
output value of
master channel
Manipulated output
value of slave channel
Manipulated output
value of master channel
Output distribution ratio
Communication
Slave channel
(Internal communication)
Capture the output value
DO output distribution bias
DO output limiter
Output
Manipulated output
value of slave channel
DO output distribution ratio
Slave channel
Communication
Manipulated
output value of
master channel
Z-DIO module *
* Distribution output from Z-DIO module becomes
open collector output or relay contact output.
The manipulated output values of the master channel and slave channels are each output within
the limit of the output limiter.
The output distribution function only functions within modules that are connected together (SRZ unit).
Continued on the next page.
Summary of Contents for Z-TIO-G
Page 8: ...i 6 IMS01T28 E4 MEMO...
Page 16: ...IMS01T28 E4 1 8 MEMO...
Page 22: ...2 6 IMS01T28 E4 MEMO...
Page 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Page 52: ...5 14 IMS01T28 E4 MEMO...
Page 82: ...7 18 IMS01T28 E4 MEMO...
Page 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Page 216: ...10 6 IMS01T28 E4 MEMO...
Page 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Page 230: ...11 14 IMS01T28 E4 MEMO...
Page 244: ...A 4 IMS01T28 E4 MEMO...
Page 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...