Table 15-3 PowerGen Error Messages, User Clearable
Fault Code
Description
Possible Causes
2003
Heater head temperature too
high
Heater head temperature
reached the maximum
allowed limit.
Hall noise, power limit too low
when blower rate is at
minimum, incorrect HHT offset
calibration, wrong converter
file loaded, bad engine.
• Review engine frequency
data, if it is not stable,
add ferrite bead.
• Calibrate HHT offset.
• If blower was at min rate
(20%) Increase QEC power
limit.
2004
Internal E-Stop signal was
activated
The internal E-Stop signal was
pulled low by the QEC, FEB or
CANBUS interface, bad
CANBUS wiring, typically
accompanied with additional
faults.
Unplug harness on both ends,
measure resistance between
Ground and 5V pin (first and
last pin).
2010
Pump feedback reading is out
of range
Feedback is outside of the
normal operating range
(1-69%) during startup self
check.
Noise on pump wiring, bad
pump signal wiring, bad pump
electronics, bad FPC firmware
or hardware
• Refer to 2016 and 2017 for
corrective actions.
• Refer to 1011 for feedback
signal explanation.
Summary of Contents for PowerGen 5650 Series
Page 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Page 8: ...iv...
Page 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Page 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Page 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Page 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Page 194: ...POWERGEN OPTIONAL FEATURE SETS 182...