C
OMMISSIONING
P
ROCEDURE
99
Table 12-5 Modbus, System Faults/Warnings
Access
(Read,
Write,
Clear)
Modbus
Register
Read
(03)
Modbus
Register
Write
(06)
Type Size
Description
Notes
R
40002
UINT
16
bit
Number of present
faults
R/W
40003
40003
UINT
16
bit
Selected fault
Write the index to select a
fault
R/C
40004
40004
UINT
16
bit
Selected fault value Clear faults by writing “0.”
Clear advanced faults by
writing the password.
Table 12-6 Modbus, Configuration
Access
(Read,
Write,
Clear)
Modbus
Register
Read (03)
Modbus
Register
Write (06)
Type
Size
Description
Units
R/W
40005
40005
INT
16 bit
GHT max supply temp
[°C]*10
R/W
40006
40006
INT
16 bit
GHT return set point
[°C]*10
R/W
40007
40007
UINT
16 bit
Maximum blower PWM
[%]
R/W
40008
40008
UINT
16 bit
HHT offset
{n}*100
Table 12-7 Modbus, FEB I/O Configuration
Access
(Read,
Write,
Clear)
Modbus
Register
Read
(03)
Modbus
Register
Write
(06)
Type
Size
Description
Notes
R/W
40041
40041
UINT
16 bit
Input select
Range 1-6, or 0 to deselect
R/W
40042
40042
ENUM
16 bit
Input function
See ENUM table
R/W
40043
40043
UINT
16 bit
Output select
Range 1-8, or 0 to deselect
R/W
40044
40044
ENUM
16 bit
Output function See ENUM table
Summary of Contents for PowerGen 5650 Series
Page 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Page 8: ...iv...
Page 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Page 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Page 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Page 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Page 194: ...POWERGEN OPTIONAL FEATURE SETS 182...