C
OMMISSIONING
P
ROCEDURE
107
12.11 QEC CONFIGURATION FOR LOAD-FOLLOWING
40045 - System
operation state
ACTIVATING
1
Unit is starting up, engine is
not producing power yet.
ENABLED
2
Unit is operating and
producing power
DEACTIVATING
4
Unit is shutting down.
DISABLED
5
Unit is disabled, waiting for
activation signal.
FAULTED
6
Unit is disabled and in fault
condition.
BOOTLOADER
8
System is disabled and in the
process of uploading firmware
to be uploaded.
STANDBY
14
System is waiting for external
input such a gas pressure to
self start.
GO_TO_STANDBY
15
System disabling because a
condition is not met, such as
insufficient gas pressure.
FILL_SEQ_INPROCESS
17
Coolant fill sequence initiated
to remove air from coolant
piping.
FILL_SEQ_ABORTED
18
Coolant fill sequence aborted.
FILL_SEQ_DONE
19
Coolant fill sequence
completed.
Table 12-11 Modbus, ENUM
Register
Name
Value
Description
CAUTION:
Disconnect customer electrical load prior
to enabling the PowerGen for the first time and
while setting-up QEC Load-following parameters.
Contact Qnergy Customer Support if unfamiliar
about how to correctly setup the PowerGen,
Qnergy Lynx, Load-following parameters:
+1(801)413-7668 (Customer Support Hotline)
Summary of Contents for PowerGen 5650 Series
Page 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Page 8: ...iv...
Page 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Page 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Page 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Page 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Page 194: ...POWERGEN OPTIONAL FEATURE SETS 182...