P
OWER
G
EN
O
PERATION
164
Table 20-1 System Run Light
Condition
Indication
Description
ON
PowerGen Base running
Power available
Fast
Continuous
Blinking
PowerGen is currently starting Power is not available at this stage
1 short blink
every 3
seconds
PowerGen is currently
deactivating
Power is not available at this stage
3 short blinks
every 3.5
seconds
PowerGen is in standby
May be started either locally or remotely
(depends on condition of ‘Local/Remote’
selector switch)
OFF
Not running and NOT ready to
start
A fault may be present (see “Fault
Messages, PowerGen”) or no power
from internal 12V battery
Table 20-2 Start/Stop (Reset) Push Button
Start/Stop (Fault Reset) Pushbutton
The Start/Stop pushbutton is only active if the local/remote selector switch is on the ‘Local’
mode.
Push the Start/Stop pushbutton to toggle between “On” and “Off”.
Push and hold the Start/Stop (Fault Rest) push button for => 15 sec. to reset fault.