F
AULT
M
ESSAGES
, P
OWER
G
EN
132
11505
Too many hall direction
changes detected
Noise
11506
Bump initiated when engine
was already bumping
Firmware issue
11507
System cannot run if the stall
is engaged
QEC haw failure
11508
Engine failed to start in given
time
Burner issue, QEC hardware
failure, engine pressure too
low
11509
Engine overstroke was
detected
Firmware issue, noise, QEC
hardware failure
11510
Piston position measurement
is bad
Hall calibration is wrong,
Firmware issue
12001
Positive or negative DC buses
fail to reach setpoint during
BBI operation
Battery is bad, QEC hardware
failure
12002
Positive bus voltage too low
Battery is bad, ADC calibration
not done, QEC hardware
failure
12003
Positive bus voltage ripple too
high
ADC calibration not done, QEC
hardware failure
12004
Negative bus voltage too low
Battery is bad, ADC calibration
not done, QEC hardware
failure
12005
Negative bus voltage ripple
too high
ADC calibration not done, QEC
hardware failure
12006
Engine running detected while
QEC is disabled
ADC calibration not done,
engine already running, QEC
hardware issue, burner issue,
firmware issue
Table 15-7 QEC Error Messages, QEC 3 (Firmware 2.X.X)
Fault Code
Description
Possible Causes
Summary of Contents for PowerGen 5650 Series
Page 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Page 8: ...iv...
Page 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Page 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Page 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Page 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Page 194: ...POWERGEN OPTIONAL FEATURE SETS 182...