F
AULT
M
ESSAGES
, P
OWER
G
EN
133
12007
E-Stop is active
Internal E-stop triggered. Can
be caused by 12V supply to
FEB pulled low. Check loads on
12V supply to FEB (gas valve
Heater, etc.). On a QEC3.0 this
may be caused by low battery
voltage.
It is also possible that the
external E-stop was triggered.
A “1” in the ‘ExtEstop’ column
of the SmartView log indicates
that the external E-stop was
pulled low. Remove external
E-stop and verify that the fault
doesn't return.
12008
Low battery
Check 12V power leads are
securely tied to battery posts.
Not enough power available
for auxiliary loads and
charging the battery.
12009
Battery is too hot or cold for
operation
Battery out of temperature
operating range
12010
Battery needs service
Battery performance is bad
12011
‘OUT_A’ current greater than
hardware current limit
Output settings are wrong,
QEC hardware failure
12012
‘OUT_B’ current greater than
hardware current limit
Output settings are wrong,
QEC hardware fialure
12013
‘OUT_C’ current greater than
hardware current limit
Output settings are wrong,
QEC hardware failure
13001
Coolant temperature too high
External loop switched off &
engine is running, aux output
off, temp sensor bad, QEC
hardware failure, coolant leak,
pump failure
13002
Coolant temperature is too
low
Temp sensor bad, QEC
hardware failure
Table 15-7 QEC Error Messages, QEC 3 (Firmware 2.X.X)
Fault Code
Description
Possible Causes
Summary of Contents for PowerGen 5650 Series
Page 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Page 8: ...iv...
Page 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Page 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Page 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Page 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Page 194: ...POWERGEN OPTIONAL FEATURE SETS 182...