7. Disconnect customer electrical load from PowerGen prior to enabling the PowerGen for the
first time.
8. Start the PowerGen by clicking
Enable
in Qnergy Lynx.
Figure 12-17 FPC Tab, Enable
If the PowerGen does not start (ignition failure fault): Adjust the #3 screw (shown in Figure
12-13 on page 84) counter-clockwise a half a turn to start with a richer combustion. This can be
repeated up to six times. If unit still does not ignite, contact Qnergy customer support, (801)
413-7668.
9.Under the QEC/Config Tab Set
Minimum Engine Power to 5000W
, Click Set,
while the
PowerGen is running
.
WARNING:
Disconnect customer electrical load
prior to enabling the PowerGen for the first time
and while setting-up QEC Load-following
parameters.
Contact Qnergy Customer Support if unfamiliar
about how to correctly setup the PowerGen,
Qnergy Lynx, Load-following parameters:
+1(801)413-7668
(Customer Support Hotline).